Boiler feedwater and membrane deaeration: removing oxygen before it removes the boiler

อ่าน 7 นาที

Every boiler in Thailand — the sugar mills' bagasse boilers, the industrial estates' package boilers, the power plants' heat-recovery steam generators — is fed with water that has had its oxygen removed. Oxygen in feedwater corrodes the economiser, the tubes and the drum by pitting, the kind of localised attack that perforates a tube wall in months while the rest of the metal looks new. The water treatment standards call for dissolved oxygen below 7 ppb in feedwater for high-pressure boilers, below 20–50 ppb for low-pressure plant, and the machine that achieves most of that is a deaerator. Increasingly, in the semiconductor, pharmaceutical and beverage industries, the same job is done at ambient temperature by a membrane contactor — and both kinds of deaerator need a vacuum pump.

1. How deaeration works

Henry's law: the concentration of a gas dissolved in water is proportional to the partial pressure of that gas in the atmosphere in contact with it. Water in contact with air at 25 °C holds about 8 ppm of oxygen. Reduce the oxygen partial pressure above the water toward zero and the dissolved oxygen leaves. Two ways to do that:

  • Thermal (steam) deaeration: heat the water to its boiling point at the deaerator pressure (102–110 °C at 1.1–1.4 bar absolute in the usual pressurised design), spray or cascade it over trays through a counter-flow of steam. The steam displaces the air; the gas solubility at the boiling point is near zero; the steam-and-gas mixture vents from the top. No vacuum pump in a pressurised deaerator — the vent is above atmospheric. But a vacuum deaerator, running at 100–300 mbar so the water boils at 45–70 °C, does the same thing with low-grade heat or none, and needs a pump to remove the stripped gas and the vapour that leaves with it.
  • Vacuum / membrane deaeration: pass the water on one side of a gas-permeable hollow-fibre membrane; apply vacuum (and often a small sweep of nitrogen) on the other; dissolved gases diffuse through the fibre wall into the vacuum. Ambient temperature, no steam, compact — a 50 m³/h contactor is the size of a filing cabinet. The vacuum pump removes the gas and sweep nitrogen.

Why does the membrane contactor still need a pump if the membrane does the work?

Because the membrane only provides the surface across which the gas moves; the driving force is the difference in oxygen partial pressure between the water and the gas side of the fibre. With air on the gas side the driving force is zero — nothing happens. The vacuum pump pulls the gas side down to 30–80 mbar absolute, reducing the oxygen partial pressure there to a few millibar, and the sweep nitrogen reduces it further toward zero by dilution. The pump removes exactly what leaves the water (oxygen, nitrogen, CO₂ — a few litres per cubic metre) plus the sweep gas plus water vapour that passes the hydrophobic membrane as vapour. Without the pump the contactor is a very expensive pipe.

2. Vacuum deaerators

A vacuum deaerator is a column at 100–300 mbar with spray nozzles or packing, often in two stages, fed with make-up water at 30–40 °C (Thai supply temperature) or warmed with waste heat. The water leaving reaches 20–100 ppb oxygen in a single stage, lower with a scavenger dose. It is used where steam is not available or is too valuable, where the water must stay cool (process and cooling water), and in the sugar industry for imbibition water.

The pump duty is the one in beverage water deaeration, scaled up:

  • Gas stripped from the water: about 20 L of air per m³ of air-saturated water (oxygen and nitrogen together) — for 100 m³/h, 2 Nm³/h.
  • Air leakage into the column and its seals: 2–10 Nm³/h.
  • Water vapour: the gas leaves saturated at the water temperature; at 150 mbar and 35 °C (vapour pressure 56 mbar) the vapour is 37 % of the gas volume; at 80 mbar it is 70 %.

For a 100 m³/h deaerator at 100 mbar, 35 °C: ~8 Nm³/h × (1,013/100) × (308/273) × (100/44) ≈ 210 m³/h at the inlet — an LM230-120 (230 m³/h), stainless, with the seal water cooled so the pump's ultimate stays under the column pressure. The liquid ring pump is the natural choice: the gas is wet, the pump may take an occasional slug when a level control fails, and its seal water can be a loop off the deaerated water itself.

3. Membrane contactors

The hollow-fibre contactor (polypropylene fibres, water on the shell or lumen side) runs with the gas side at 30–80 mbar and a nitrogen sweep of 0.1–1 Nm³/h per module, and achieves < 1 ppb oxygen in two or three stages — which is why the semiconductor fabs use it for ultrapure water, and the pharmaceutical plants for WFI pre-treatment. Beverage plants use it to remove CO₂ from water before carbonation-level control, and to add CO₂ or nitrogen (the same membrane, run the other way).

The pump duty per module:

  • Stripped gas: 15–20 L per m³ of water → for a 50 m³/h skid, ~1 Nm³/h.
  • Sweep nitrogen: 0.5–2 Nm³/h per skid.
  • Water vapour through the membrane: the gas leaves saturated at the water temperature; at 50 mbar and 25 °C (vapour pressure 32 mbar) two-thirds of the gas volume is vapour — and the vapour is what limits how low the pump can take the gas side. At 32 mbar the gas side cannot go below the water's own vapour pressure regardless of the pump.
  • Leakage: small — the skid is compact and welded.

Total: ~3 Nm³/h of gas and sweep at 50 mbar with vapour → roughly 180 m³/h at the inlet for a 50 m³/h skid. Contactor manufacturers specify liquid ring pumps of 100–300 m³/h per skid, or dry pumps where the water must not contact a seal liquid:

  • Liquid ring (LM200-065, LM230-120): tolerant of the vapour, cheap, and — on a water-treatment skid — the seal water is the product water, so the loop is simple. Its 33 mbar ultimate (cool water) matches the membrane's 30–50 mbar operating point; chilled seal water, or an ejector stage, where the skid runs at 30 mbar.
  • Dry claw (CL300, 50 mbar ultimate) or dry screw (DSI150) on ultrapure-water and pharma skids where no seal water is wanted and the vapour is handled by the dry pump's heat and a drain.

4. Seal water and materials

The gas from a deaerator is water-saturated and carries dissolved CO₂ released from the water — the condensate in the pump is slightly acidic (carbonic acid), and on a plant deaerating softened or RO water the condensate is also very low in dissolved solids and therefore aggressive to carbon steel. Stainless steel liquid ring pumps throughout; seal water in a closed loop from the deaerated water (so the pump does not re-aerate the product and no fresh water is consumed) through a cooler against the plant's cooling water; a separator returning condensate to the deaerator inlet.

Seal water temperature governs capacity as it does on every liquid ring duty — a deaerator at 100 mbar on a pump with 35 °C seal water (ultimate ~65 mbar) is working at a third of its nominal capacity; cooled to 20 °C it has most of it. Where plant cooling water is 32 °C (it is), a small chiller on the seal water loop is the cheapest capacity available.

5. Worked plants

Plant Water Method Pressure Dr.Vakuum answer
Industrial estate boiler house, 30 m³/h make-up Softened Vacuum spray deaerator, 2-stage 120 mbar LM200-065, stainless, cooled seal loop
Sugar mill, 200 m³/h imbibition and make-up Raw/clarified Vacuum deaerator 150 mbar LS275-220 (650 m³/h), stainless
Semiconductor UPW, 60 m³/h Ultrapure 3-stage membrane, N₂ sweep 40 mbar DSI150 dry screw, or CL300
Brewery blending water, 80 m³/h Treated 2-stage membrane, CO₂ sweep 50 mbar LM230-120, chilled seal water
Pharma WFI pre-treatment, 20 m³/h RO permeate Membrane, N₂ sweep 40 mbar CL300 oil-free, or DSI150
Power plant condensate polishing, 150 m³/h Condensate Vacuum deaerator 100 mbar LS275-220

Recommended Dr.Vakuum machines

Liquid ring monobloc (LM Series), stainless — deaerators and membrane skids to 100 m³/h of water: LM145-080, LM200-065, LM230-120, LM270-155.

Liquid ring single-stage (LS Series) — large deaerators: LS275-220, LS410-320.

Dry claw (CL Series) and dry screw (DSI Series) — ultrapure and pharma membrane skids without seal water: CL300, DSI150.

The condenser at the other end of the steam cycle has its own air removal duty — see Power plant condenser air extraction.

Water flow to pump. Tell us the water flow and temperature, the oxygen target and whether the deaerator is a vacuum column or a membrane skid with sweep gas, and we will size the pump and its seal water cooling. Talk to an engineer.