Transformer oil degassing and dehydration: the vacuum side of an oil treatment plant

อ่าน 7 นาที

Thailand's grid runs on tens of thousands of oil-filled transformers, and every one of them is filled with oil that has been vacuum-treated, then treated again at intervals through its life. Transformer oil purification — filtration, dehydration and degassing — is a vacuum process at its heart: hot oil is spread as a thin film inside a chamber at a few millibar, and the water and gases dissolved in it flash out. The plants are built in fixed form at transformer factories and oil regeneration shops, and in mobile form on trailers that visit substations. The vacuum set is the part of the plant that decides how dry and how gas-free the oil comes out.

1. What the oil has to lose

New mineral insulating oil from the refinery, and oil in a service transformer, carry:

  • Dissolved water: 20–60 ppm in service oil; the specification for oil going into a transformer is < 10 ppm, typically < 5 ppm. Water in the oil migrates into the paper insulation and halves its life for every doubling of moisture.
  • Dissolved gas: oil in contact with air is saturated at about 10 % gas by volume (mostly nitrogen and oxygen); the target is < 0.1–0.5 %, so that gas does not come out of solution as bubbles in a high-field region and start a partial discharge.
  • Particles: metal, carbon, cellulose fibres — removed by the plant's filters, not by vacuum.
  • Acids and sludge (in aged oil): removed by regeneration (clay contact), a separate process.

Dehydration and degassing are the same physical step. Vacuum lowers the partial pressure of water vapour and gases above the oil film toward zero, and both diffuse out of the thin film in seconds. Heating the oil to 50–70 °C helps on two counts: it raises water's vapour pressure (from 23 mbar at 20 °C to 200 mbar at 60 °C) so it leaves faster, and it lowers the oil's viscosity so the film is thinner.

Why can the degassing chamber not go deeper than about 0.5 mbar?

Because transformer oil itself has a vapour pressure. Mineral insulating oil's light fractions begin to evaporate at roughly 10⁻²–10⁻¹ mbar at 60 °C; pull the chamber below about 0.5 mbar and the plant starts to distil the oil's own light ends into the vacuum pump, losing oil, changing its properties and contaminating the pump. Plants therefore run the degasser at 0.5–5 mbar — deep enough that water and air leave the film almost completely, shallow enough that the oil stays. The ultimate pressure of the pump set must be well below this (10⁻² mbar or better) so the set has the speed to hold 1–2 mbar against the load; the pressure is held there by a controller, not by the pump's limit.

2. The load on the vacuum set

Per cubic metre of oil treated:

  • Water: removing 40 ppm from 1 m³ (870 kg) of oil is 35 g of water. At 3,000 L/h that is ~105 g/h — tiny by mass.
  • Gas: removing 10 % by volume is 100 L of air per m³ of oil; at 3,000 L/h, 300 L/h ≈ 0.3 Nm³/h.
  • Air leakage into a degassing column at 1 mbar with its sight glasses, level control glands and oil pump seals: 1–3 Nm³/h on a fixed plant, more on a mobile one after a few years on the road.

So the mass flow is small — a few Nm³/h — but at 1 mbar each Nm³ is a thousand cubic metres of actual volume. Three Nm³/h of gas plus 105 g/h of water vapour (about 150 m³/h at 1 mbar and 50 °C) at 1 mbar and 50 °C is roughly

(3 × 1,013 × 323/273) + 150 ≈ 3,500 m³/h of actual volume at 1 mbar

That is a Roots booster duty. The set that nearly every oil plant uses: a booster of 1,000–4,000 m³/h at the inlet, backed by a two-stage oil-sealed rotary vane pump whose ultimate (5 × 10⁻³ mbar) leaves two decades of headroom under the 1 mbar process pressure and whose gas ballast handles the water. For a 3,000 L/h plant an MB300 (1,000 m³/h) on a DV90 or DV175; for 6,000 L/h an MB600 on a DV175; for 10,000 L/h and above an MB1200 on a DV275, or two MB600/DV175 sets for a mobile plant that needs redundancy at a substation.

The booster also protects the backing pump: the water vapour passes through the booster (which runs warm) and reaches the backing pump at 5–10 mbar, where the backing pump's ballast handles it comfortably.

3. Oil carry-over and foam

The gas leaving the degassing chamber carries oil mist — the film is sprayed or run over packing, and a mist is unavoidable — and, when wet or new oil is treated too fast, foam. Oil mist in a booster coats the rotors (harmless for a while); oil in the backing pump's oil is, perversely, the problem: transformer oil and pump oil are both mineral oils but of different viscosities and additive packages, and the mixture degrades the pump's sealing and ultimate. Design:

  • A demister pad or coalescing element in the degassing chamber's gas outlet.
  • A knock-out pot with a sight glass and a return line to the oil inlet between chamber and booster — what collects there is transformer oil and goes back into the process.
  • Foam control: a level switch high in the chamber that throttles the oil inlet; a slower first pass on very wet oil; anti-foam is not used (it contaminates the oil).
  • Exhaust oil mist separator on the backing pump, with its drain to waste — not back to the pump, since that oil is now mixed.
  • Change the backing pump oil by condition (viscosity or appearance), typically every 300–500 hours on a busy plant.

Dry screw backing pumps (DSI150, DSI300) remove the oil-mixing problem entirely and are the choice on new fixed plants at transformer factories; their 0.05 mbar ultimate is sufficient under a booster for a 1 mbar process. Mobile plants mostly keep the two-stage vane pump for its size, weight and tolerance of being transported.

4. Mobile plants

A trailer-mounted plant treating a transformer in situ — oil circulated from the transformer's bottom valve through heater, filter and degasser and back to the top — adds constraints:

  • Weight and footprint: an MB600 + DV175 set is about 450 kg; a dry screw adds more.
  • Site power: often a 50 kVA generator — the booster's 7.5 kW plus the backing pump's 5.5 kW plus the heater (30–60 kW) sets the generator size; a VSD on the booster softens the start.
  • Transport: pumps drained, inlet and exhaust sealed, mounted on anti-vibration mounts; a two-stage vane pump tolerates this; a dry screw's rotor clearances do not like being bounced on a Thai provincial road unless properly mounted.
  • The transformer tank is frequently evacuated by the same set during filling (see vacuum impregnation), so the set is sized for the larger of the two duties — usually the tank evacuation, which wants the booster's full speed.

5. Worked plants

Plant Oil flow Degasser pressure Gas + vapour load at 1 mbar Dr.Vakuum set
Small mobile, distribution transformers 1,500 L/h 1–2 mbar ~1,500 m³/h MB150 + DV60
Standard mobile, substation 3,000–4,000 L/h 1 mbar ~3,500 m³/h MB300 + DV175
Large mobile / factory 6,000 L/h 0.5–1 mbar ~6,000 m³/h MB600 + DV175 or DSI150
Transformer factory, fixed 10,000 L/h + tank evacuation 0.5 mbar ~10,000 m³/h MB1200 + DSI300
Oil regeneration shop 5,000 L/h, aged oil, foam 2 mbar ~5,000 m³/h MB600 + DV275, large knock-out

Recommended Dr.Vakuum machines

Roots boosters (MB Series) — the inlet stage, sized on actual volume at 1 mbar: MB150 (500 m³/h), MB300 (1,000 m³/h), MB600 (2,000 m³/h), MB1200 (4,140 m³/h).

Two-stage oil-sealed vane (DV Series) — backing, with ballast and mist separator: DV60, DV90, DV175, DV275.

Dry screw (DSI Series) — backing on fixed plants, no oil mixing: DSI150, DSI300.

The staging and cut-in rules for the booster are in When a Roots booster pays.

Plant to set. Tell us the oil flow, the degasser pressure and whether the plant is mobile, and we will size the booster and backing pump with the knock-out and mist handling. Talk to an engineer.